36 & 72.5kV Dry Air Insulated VCB |
|
Features• No Usage of SF6 GasPressurized dry air is employed as insulatring medium • Long Operation Life Without inspection of main contacts, VCB is capable of: - 10 000 rated current breaking - 20 Full fault current breaking • Easier Maintenance than GCB Vacuum interrupter has self arc extinguishing characteristics • Superior Performance in Cold Region Applicable ambient temperature without tank heater: -50~40°C |
![]() |
|
![]() |
Specifications 36kV |
||
Type designation | NVBOA-30732B | |
Applicable standards |
IEC-62271-100 (2008) | |
Rated voltage (kV) | 36 |
|
Rated current (A) |
2000 | |
Rated frequency (Hz) | 50 / 60 | |
Insulation level | 1 min. power frequency (kV ms) | 70 |
1.2 x 50µs impulse (kV peak) | 200 | |
Rated short time withstand current (kA-sec) | 31.5-3 | |
Rated peak withstand current (kA peak) | 82 | |
Dry air pressure | Rated pressure (MPa) | 0.50 |
Low pressure alarm (MPa) | 0.45 | |
Low pressure lockout (MPa) | 0.40 | |
Rated operating sequence | Open - 0.3 sec -Close Open - 3 min - Close Open | |
Mass without CTs (kg) | 1500 |
Specifications 72.5kV |
|||
Type designation | NVBOA-60732B | NVBOA-60740B | |
Applicable standards |
ANSI c37.06, IEC 62271-100 | ||
Rated voltage (kV) | 72.5 |
||
Rated current (A) |
2000 | ||
Rated frequency (Hz) | 50 / 60 | ||
Insulation level | 1 min. power frequency (kV ms) | 160 | |
1.2 x 50µs impulse (kV peak) | 350 | ||
Rated short time withstand current (kA-sec) | 31.5-3 | 40-3 | |
Rated peak withstand current (kA peak) | 82 | 108 | |
Dry air pressure | Rated pressure (MPa) | 0.50 | |
Low pressure alarm (MPa) | 0.45 | ||
Low pressure lockout (MPa) | 0.40 | ||
Rated operating sequence | Open - 0.3 sec -Close Open - 3 min - Close Open | ||
Mass without CTs (kg) | 1900 |