Basic Operating Parameters |
R~L-GSE |
Rated Frequency |
50/60Hz |
Rated cubicle (auxiliary) supply voltage |
85 to 265 V AC/DC |
Rated operating sequence |
0-0.1s-C0-1s-C0-1s-C0-60s |
Degree of protection |
IP54 |
Temperature range |
-40°C to +55°C |
Maximum humidity |
100 % |
Maximum altitude above sea level |
2000 m |
Vibration endurance (Pole mounted) |
IEC 60255-21-1 Class 1, test acceleration 1.5g |
Vibration response (Pole mounted) |
IEC 60255-21-1 Class 2 |
Shock response (Pole mounted) |
IEC 60255-21-2 Class 1 |
Bump |
GOST 17516.1-90, class M7, GOST 16962.2-90 |
Seismic |
IEC 60255-21-3 Class 1 |
Operating time after loss of auxiliary supply , hours, not less: (Without providing power for RTU and USB, without IOM, CPM off) |
|
- at +25°C |
48 |
- at -40°C |
12 |
- at +55°C |
48 |
RTU power supply: |
|
- voltage range |
5 to 15 V, step 0.5 V |
- max output power |
15 w |
- max output power at 0.5 duty cycle (range 12-15 V) |
30W |
Maximum power consumption of RC from auxiliary supply |
60W |
Weight |
29 kg (Battery, IOM and RTU not included) |
Dimensions |
450x860x390 mm |