Features
• No Usage of SF6 Gas Pressurized dry air is employed as insulating medium • Long Operation Life Without inspection of main contacts, VCB is capable of: – 10 000 rated current breaking – 20 Full fault current breaking • Easier Maintenance than GCB Vacuum interrupter has self arc extinguishing characteristics • Superior Performance in Cold Region Applicable ambient temperature without tank heater: -50~40°C | ![]() |
![]() |
Specifications 36kV
Type designation | NVBOA-30732B | ||
Applicable standards | IEC-62271-100 (2008) | ||
Rated voltage (kV) | 36 | ||
Rated current (A) | 2000 | ||
Rated frequency (Hz) | 50 / 60 | ||
Insulation level | 1 min. power frequency (kV ms) | 70 | |
1.2 x 50µs impulse (kV peak) | 200 | ||
Rated short time withstand current (kA-sec) | 31.5-3 | ||
Rated peak withstand current (kA peak) | 82 | ||
Dry air pressure | Rated pressure (MPa) | 0.50 | |
Low pressure alarm (MPa) | 0.45 | ||
Low pressure lockout (MPa) | 0.40 | ||
Rated operating sequence | Open – 0.3 sec -Close Open – 3 min – Close Open | ||
Mass without CTs (kg) | 1500 |
Specifications 72.5kV
Type designation | NVBOA-60732B | NVBOA-60740B |
Applicable standards | ANSI c37.06, IEC 62271-100 | |
Rated voltage (kV) | 72.5 | |
Rated current (A) | 2000 | |
Rated frequency (Hz) | 50 / 60 | |
Insulation level | 1 min. power frequency (kV ms) | 160 |
1.2 x 50µs impulse (kV peak) | 350 | |
Rated short time withstand current (kA-sec) | 31.5-3 | 40-3 |
Rated peak withstand current (kA peak) | 82 | 108 |
Dry air pressure | Rated pressure (MPa) | 0.50 |
Low pressure alarm (MPa) | 0.45 | |
Low pressure lockout (MPa) | 0.40 | |
Rated operating sequence | Open – 0.3 sec -Close Open – 3 min – Close Open | |
Mass without CTs (kg) | 1900 |